Based on the statistical data of cable tunnel fire accidents at home and abroad in recent years
the causes and characteristics of cable tunnel fire accidents are summarized and the various fire extinguishing systems are introduced
such as water spray fire extinguishing system
high-pressure water mist fire extinguishing system
gas fire extinguishing system
aerosol fire extinguishing system and ultra-fine dry powder extinguishing system. According to the analysis of technology and economics
it is recommended to adopt the high-pressure water mist fire extinguishing system in the longdistance and largevolume cable tunnels
and the ultrafine dry powder fire extinguishing system is recommended in the cable joints or other key protection areas for local fire extinguishing. However
it is not recommended to use gas fire extinguishing system
water spray fire extinguishing system and aerosol fire extinguishing system in longdistance and large-volume cable tunnels.